15-25kV XLPE-PVC Sheathed Unarmoured Power Cable 100 Levels
100% Insulation Levels (single conductor)
Conductor |
Insulation thickness ( mm ) |
Sheath thickness ( mm ) |
Overall Dia. approx. ( mm ) |
AC Test voltage ( kV / 5 min ) |
Cable weight approx. ( kg / km ) |
||
Size (AWG or MCM) |
Construction ( No. / mm ) |
Outside Dia. ( mm ) |
|||||
1 1/0 2/0 3/0 4/0 |
19/1.69 C.C. C.C. C.C. C.C. |
8.43 8.53 9.55 10.74 12.07 |
6.60 6.60 6.60 6.60 6.60 |
2.03 2.03 2.03 2.03 2.03 |
30.6 30.7 31.7 32.9 34.2 |
38 38 38 38 38 |
1229 1331 1499 1706 1961 |
250 300 350 400 500 |
C.C. C.C. C.C. C.C. C.C. |
13.21 14.48 15.65 16.74 18.69 |
6.60 6.60 6.60 6.60 6.60 |
2.03 2.03 2.03 2.03 2.03 |
35.3 36.6 37.8 38.9 40.9 |
38 38 38 38 38 |
2187 2465 2739 3019 3559 |
550 750 1000 |
C.C. C.C. C.C. |
20.65 23.06 26.92 |
6.60 6.60 6.60 |
2.79 2.79 2.79 |
44.5 47.0 50.8 |
38 38 38 |
4305 5108 6444 |
100% Insulation Levels (Three conductor)
Conductor |
Insulation thickness ( mm ) |
Sheath thickness ( mm ) |
Overall Dia. approx. ( mm ) |
AC Test voltage ( kV / 5 min ) |
Cable weight approx. ( kg / km ) |
||
Size (AWG or MCM) |
Construction ( No. / mm ) |
Outside Dia. ( mm ) |
|||||
1 1/0 2/0 3/0 4/0 |
19/1.69 C.C. C.C. C.C. C.C. |
8.43 8.53 9.55 10.74 12.07 |
6.60 6.60 6.60 6.60 6.60 |
2.79 2.79 2.79 2.79 3.56 |
62.3 62.5 64.7 67.2 71.8 |
38 38 38 38 38 |
4117 4425 4975 5646 6765 |
250 300 350 400 |
C.C. C.C. C.C. C.C. |
13.21 14.48 15.65 16.74 |
6.60 6.60 6.60 6.60 |
3.56 3.56 3.56 3.56 |
74.2 77.0 79.5 81.8 |
38 38 38 38 |
7501 8396 9236 10193 |
133% Insulation Levels (single conductor)
Conductor |
Insulation thickness ( mm ) |
Sheath thickness ( mm ) |
Overall Dia. approx. ( mm ) |
AC Test voltage ( kV / 5 min ) |
Cable weight approx. ( kg / km ) |
||
Size (AWG or MCM) |
Construction ( No. / mm ) |
Outside Dia. ( mm ) |
|||||
1 1/0 2/0 3/0 4/0 |
19/1.69 C.C. C.C. C.C. C.C. |
8.43 8.53 9.55 10.74 12.07 |
8.76 8.76 8.76 8.76 8.76 |
2.03 2.03 2.03 2.03 2.03 |
35.3 35.4 36.4 37.6 38.9 |
49 49 49 49 49 |
1492 1595 1769 1985 2249 |
250 300 350 400 500 |
C.C. C.C. C.C. C.C. C.C. |
13.21 14.48 15.65 16.74 18.69 |
8.76 8.76 8.76 8.76 8.76 |
2.03 2.03 2.03 2.79 2.79 |
40.1 41.5 42.6 45.4 47.3 |
49 49 49 49 49 |
2484 2777 3059 3527 4081 |
550 750 1000 |
C.C. C.C. C.C. |
20.65 23.06 26.92 |
8.76 8.76 8.76 |
2.79 2.79 2.79 |
49.3 51.8 55.9 |
49 49 49 |
4672 5496 6883 |
133% Insulation Levels (Three conductor)
Conductor |
Insulation thickness ( mm ) |
Sheath thickness ( mm ) |
Overall Dia. approx. ( mm ) |
AC Test voltage ( kV / 5 min ) |
Cable weight approx. ( kg / km ) |
||
Size (AWG or MCM) |
Construction ( No. / mm ) |
Outside Dia. ( mm ) |
|||||
1 1/0 2/0 3/0 4/0 |
19/1.69 C.C. C.C. C.C. C.C. |
8.43 8.53 9.55 10.74 12.07 |
8.76 8.76 8.76 8.76 8.76 |
3.56 3.56 3.56 3.56 3.56 |
74.2 74.4 76.6 79.2 82.0 |
49 49 49 49 49 |
5396 5707 6287 6993 7875 |
250 300 350 400 |
C.C. C.C. C.C. C.C. |
13.21 14.48 15.65 16.74 |
8.76 8.76 8.76 8.76 |
3.56 3.56 3.56 3.56 |
84.5 87.4 89.9 92.3 |
49 49 49 49 |
8635 9604 10526 11463 |
website: www.caledonian-cables.com
email: sales@caledonian-cables.com
* C.C.: Stranded and compacted circular. |